Calculate wire gauge by ampacity, conduit fill percentage, minimum conduit size, and total wire run length for any residential or light commercial electrical circuit.
Find the correct wire gauge for your circuit based on load and breaker size.
Total connected load on circuit
W
Or enter load to find breaker
Over 3 current-carrying conductors
Wire Gauge
Insulation
Quantity
ft
2 for 120V; 3 for 240V; 4 for 3-phase
For pull tails at each box
$
YOUR RESULTS
Common Wire Gauge Quick Reference (Copper, 60°C/75°C)
AWG
Max Amps (60°C)
Max Amps (75°C)
Typical Use
14 AWG
15A
15A
Lighting, general outlets (15A breaker)
12 AWG
20A
20A
Kitchen, bath, garage (20A breaker)
10 AWG
30A
30A
Dryer, water heater (30A breaker)
8 AWG
40A
50A
Range, AC disconnect (40ā50A breaker)
6 AWG
55A
65A
Hot tub, large AC (60A breaker)
4 AWG
70A
85A
Subpanel feeder
2 AWG
95A
115A
Large subpanel feeder
1/0 AWG
125A
150A
Main service feeder
14, 12, and 10 AWG show the same value in both columns because NEC 240.4(D) caps their maximum overcurrent protection at a fixed amperage (15A/20A/30A for copper) regardless of insulation temperature rating. 10 AWG copper can carry 35A per its raw 75°C ampacity, but code does not permit a breaker larger than 30A to protect it.
ā ļø All electrical work must comply with the National Electrical Code (NEC) and local amendments. Permitted work requires inspection by a licensed electrical inspector. When in doubt, consult a licensed electrician: electrical mistakes cause fires and electrocution.
Three tools in one: Wire Gauge / Ampacity finds the correct wire size for any circuit based on load and breaker; Conduit Fill checks whether your wire bundle fits within NEC fill limits and recommends the minimum conduit size if it doesn't; Wire Run Length calculates total wire footage including conductor count, box tails, and 10% waste. All calculations reference NEC Table 310.15(B) ampacity values.
Wire Gauge and Ampacity: The Basics
Wire gauge (AWG: American Wire Gauge) runs backwards: smaller numbers mean larger wire. 14 AWG is thinner than 12 AWG; 6 AWG is much thicker than 12 AWG. Each circuit must have wire sized to handle the ampacity of its breaker. The wire is what protects from overheating if the breaker doesn't trip fast enough: undersized wire is a fire hazard, not just a code violation.
Conduit Type Comparison
Conduit Type
Best For
Cost
Notes
EMT (thin-wall metal)
Indoor commercial, exposed runs
Moderate
Most common; compression or setscrew fittings
PVC Schedule 40
Underground, wet locations, outdoor
Low
Must be glued; can't use where heat or impact expected
PVC Schedule 80
Underground where damage risk exists
Moderate
Thicker walls; smaller interior; used for direct burial
IMC (intermediate metal)
Industrial, outdoor exposed
Higher
Heavier than EMT; threaded or compression fittings
RMC (rigid metal)
Hazardous locations, service entrance
Highest
Heaviest conduit; used for service entrance conductors
Flexible metal (Greenfield)
Final connections to motors, equipment
Moderate
Limited to 6 ft; not for long runs
NEC Conduit Fill Rules
The NEC limits conduit fill to prevent heat buildup and to allow wire to be pulled without damage. For a single conductor: 53% fill maximum. For two conductors: 31% fill maximum. For three or more conductors: 40% fill maximum. These percentages apply to the interior cross-sectional area of the conduit. The Conduit Fill tab above calculates your actual fill percentage and flags NEC violations.
Common Electrical Wiring Mistakes
Using 14 AWG wire on a 20-amp breaker. 14 AWG copper is rated for 15 amps maximum. Putting it on a 20-amp breaker means the breaker won't trip until 20 amps of current: which is 33% more than the wire can safely handle. The wire overheats inside the wall where you can't see it. 20-amp circuits require 12 AWG minimum.
Not derating for more than 3 conductors in a conduit. When more than 3 current-carrying conductors share a conduit, they generate heat that reduces each wire's safe ampacity. NEC requires derating: 4ā6 conductors = 80% of rated ampacity; 7ā9 = 70%; 10+ = 50%. Skipping derating is common on conduit runs with multiple circuits: and it produces wires that run hot under load.
Overfilling conduit. Cramming too many wires into conduit makes pulling impossible, damages insulation during installation, and generates heat in use. Calculate fill before ordering conduit: it's far cheaper to step up to the next conduit size than to damage wire during a pull or rewire a job that fails inspection.
Using aluminum wire for branch circuits. Aluminum wire is acceptable for service entrances and feeder conductors to panels. It's not appropriate for standard 15A and 20A branch circuits to outlets and switches because the connection points at devices aren't designed for aluminum's thermal expansion. Only copper-clad aluminum or copper is acceptable at device terminations unless the device is specifically rated for aluminum (AL/CO marking).
Not leaving enough wire at boxes. NEC requires a minimum of 6 inches of free conductor at each box, measured from the point where the wire enters the box. Too short means the next electrician (or you, doing a repair) can't reach the wire for a safe connection. Always pull an extra foot of wire at every box during rough-in: it costs almost nothing and prevents a lot of headaches later.
Permit reminder: Most residential electrical work beyond simple device replacements requires a permit and inspection. This includes new circuits, panel work, subpanels, EV charger installations, and generator transfer switches. A licensed electrician pulls permits as part of their standard work: if yours isn't, ask why. Unpermitted electrical work creates disclosure issues when you sell and may not be covered by your homeowner's insurance if it causes a fire.
What wire gauge do I need for a 20-amp circuit? ā¾
12 AWG copper is the minimum for a 20-amp circuit: no exceptions. 14 AWG is only rated for 15-amp circuits. A 20-amp kitchen or bathroom circuit uses 12 AWG (or 12/2 NM cable with ground). If you're running the circuit in conduit with THWN wire, 12 AWG copper rated at 20 amps at 75°C is still the correct choice for a 20-amp breaker.
What is conduit fill and why does it matter? ā¾
Conduit fill is the percentage of a conduit's interior cross-sectional area occupied by wire. The NEC limits fill to 40% for three or more wires (31% for two, 53% for one) to prevent heat buildup and ensure the wire can be pulled without damaging the insulation. Overfilled conduit is a code violation, a fire hazard, and practically impossible to pull wire through. Calculate fill before ordering conduit and step up to the next size if you're over the limit.
Can I use aluminum wire in my home? ā¾
Aluminum wire is commonly used for service entrance conductors (the big wires from the meter to the main panel) and for feeder conductors to subpanels. It's not recommended for standard 15A/20A branch circuits to outlets and switches because aluminum expands and contracts more than copper, loosening connections over time and creating fire hazards. Homes built in the 1960sā70s often have aluminum branch circuit wiring: if yours does, have it inspected by a licensed electrician.
What is the 80% rule for breakers? ā¾
For "continuous loads": loads that run for 3 hours or more: the NEC requires the circuit to be loaded to no more than 80% of the breaker's rating. A 20-amp breaker on a continuous load circuit should not exceed 16 amps of connected load. This applies to things like EV chargers, electric water heaters, and HVAC equipment: all of which run for extended periods. Lighting and outlet circuits with intermittent loads don't trigger the 80% rule in most residential applications.
How do I calculate how much wire I need for a circuit? ā¾
Measure the run length from the panel to the last device. Multiply by the number of conductors (typically 3 for a 120V circuit with ground, 4 for a 240V circuit with neutral). Add 1 foot per junction box and device box for tails. Then add 10% waste. For a 50 ft run to 3 outlets (3 conductors, 3 boxes): (50 Ć 3) + (3 Ć 1) = 153 LF + 10% = 168 LF total. The Wire Run tab above does this automatically.